Teleport can connect to a number of different asset types. Here you can browse supported assets of the following types:

Contact us at support@withthegrid.com if you do not see the type of your asset.

If your asset type is not covered by the above list, it is possible to integrate assets using a a general integration. Your asset needs to meet these requirements:

  • Must be a power generating asset. The power output of the asset can be limited through Modbus.
  • The asset reports its active power output.

For this to be possible, the following Modbus registers need to be configured on the asset:

ItemStart addressSizeTypeUnitFunction codeR/WNotes
Target active power limit from modbus server321UInt160.01%0x03, 0x06R/WActive power limit as a percentage of nominal active power
Effective active power limit501UInt160.01%0x03RSetpoint confirmed by the asset.
Active power512Int32W0x03RActive power output of the asset.